ean | 4015082426774 | ||
product height | 73 mm | ||
Product weight | .12 kg | ||
certifications | ce | ||
10.11 short-circuit rating | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
rated short-circuit breaking capacity (en 60898) at 230 v | 6 ka | ||
current limiting class | 3 | ||
amperage rating | 10 a | ||
frequency rating - max | 60 hz | ||
10.8 connections for external conductors | is the panel builder's responsibility. | ||
number of poles (total) | 1 | ||
special features | ambient temperature hint: a 1 °c increase results in a 0.5% linear reduction of current carrying capacity | ||
heat dissipation per pole, current-dependent | 0 w | ||
rated switching capacity (iec/en 60898-1) | 6 ka | ||
connectable conductor cross section (solid-core) - min | 1 mm² | ||
number of poles | single-pole | ||
10.6 incorporation of switching devices and components | does not apply, since the entire switchgear needs to be evaluated. | ||
used with | pls6 miniature circuit breaker |
||
tripping characteristic | c | ||
10.13 mechanical function | the device meets the requirements, provided the information in the instruction leaflet (il) is observed. | ||
10.9.4 testing of enclosures made of insulating material | is the panel builder's responsibility. | ||
Application | switchgear for residential and commercial applications xpole - switchgear for residential and commercial applications |
||
voltage type | ac | ||
heat dissipation capacity | 0 w | ||
width in number of modular spacings | 1 | ||
10.2.3.3 resist. of insul. mat. to abnormal heat/fire by internal elect. effects | meets the product standard's requirements. | ||
connectable conductor cross section (solid-core) - max | 25 mm² | ||
Overvoltage category | iii | ||
10.7 internal electrical circuits and connections | is the panel builder's responsibility. | ||
rated impulse withstand voltage (uimp) | 4 kv | ||
connectable conductor cross section (multi-wired) - max | 25 mm² | ||
10.2.2 corrosion resistance | meets the product standard's requirements. | ||
10.2.7 inscriptions | meets the product standard's requirements. | ||
rated insulation voltage (ui) | 440 v |
product length/depth | 85 mm | ||
product width | 17.5 mm | ||
compliances | rohs conform | ||
rated operational current for specified heat dissipation (in) | 10 a | ||
10.4 clearances and creepage distances | meets the product standard's requirements. | ||
10.12 electromagnetic compatibility | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
rated short-circuit breaking capacity (en 60898) at 400 v | 6 ka | ||
10.2.5 lifting | does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.3.1 verification of thermal stability of enclosures | meets the product standard's requirements. | ||
rated short-circuit breaking capacity (iec 60947-2) at 400 v | 0 ka | ||
rated short-circuit breaking capacity (iec 60947-2) at 230 v | 0 ka | ||
ambient operating temperature - max | 75 °c | ||
built-in depth | 70.5 mm | ||
Features | additional equipment possible | ||
10.9.3 impulse withstand voltage | is the panel builder's responsibility. | ||
ambient operating temperature - min | -25 °c | ||
10.5 protection against electric shock | does not apply, since the entire switchgear needs to be evaluated. | ||
equipment heat dissipation, current-dependent | 1.5 w | ||
frequency rating - min | 50 hz | ||
10.2.6 mechanical impact | does not apply, since the entire switchgear needs to be evaluated. | ||
static heat dissipation, non-current-dependent | 0 w | ||
10.3 degree of protection of assemblies | does not apply, since the entire switchgear needs to be evaluated. | ||
number of poles (protected) | 1 | ||
release characteristic | c | ||
10.2.3.2 verification of resistance of insulating materials to normal heat | meets the product standard's requirements. | ||
10.9.2 power-frequency electric strength | is the panel builder's responsibility. | ||
Degree of protection | ip20 | ||
Pollution degree | 2 | ||
connectable conductor cross section (multi-wired) - min | 1 mm² | ||
10.10 temperature rise | the panel builder is responsible for the temperature rise calculation. eaton will provide heat dissipation data for the devices. | ||
Type | miniature circuit breaker pls6 |
||
10.2.4 resistance to ultra-violet (uv) radiation | meets the product standard's requirements. | ||
rated operational voltage (ue) - max | 230 v |