Eaton 278890

faz-d6/3

$42.29 Limited stock only available on quotation

Specifications

Mounting Position as required
Width 54 mm
Weight 329g
ean 4015082788902
product height 75.5 mm
Product weight .329 kg
certifications ul (category control number qvnu2, qvnu8)
ce marking
ul 1077
csa-c22.2 no. 235
ul (file no. e177451)
north america (ul recognized, csa certified)
iec/en 60898
csa (class no. 3215-30)
csa (file no. 204453)
iec/en 60947-2
en45545-2
iec 61373
10.11 short-circuit rating is the panel builder's responsibility. the specifications for the switchgear must be observed.
rated short-circuit breaking capacity (en 60898) at 230 v 10 ka
mounting method top-hat rail iec/en 60715
rated short-circuit breaking capacity (en 60898) at 400 v 10 ka
10.2.5 lifting does not apply, since the entire switchgear needs to be evaluated.
frequency rating - max 60 hz
10.8 connections for external conductors is the panel builder's responsibility.
number of poles (total) 3
rated short-circuit breaking capacity (iec 60947-2) at 230 v 15 ka
ambient operating temperature - max 75 °c
built-in depth 70.5 mm
lifespan, electrical 10000 operations
10.9.3 impulse withstand voltage is the panel builder's responsibility.
ambient operating temperature - min -25 °c
selectivity class 3
terminal capacity (control cable) 25 mm² (1x)
Mounting position as required
tripping characteristic d
10.13 mechanical function the device meets the requirements, provided the information in the instruction leaflet (il) is observed.
10.9.4 testing of enclosures made of insulating material is the panel builder's responsibility.
Application branch circuits, not as bcpd
switchgear for industrial and advanced commercial applications
xeffect - switchgear for industrial and advanced commercial applications
voltage type ac
frame 45 mm
heat dissipation capacity 0 w
width in number of modular spacings 3
10.2.3.2 verification of resistance of insulating materials to normal heat meets the product standard's requirements.
enclosure width 80 mm
10.9.2 power-frequency electric strength is the panel builder's responsibility.
Degree of protection ip40 (when fitted)
ip20
ul/csa type: -
ip20 (iec)
Pollution degree 2
connectable conductor cross section (multi-wired) - min 1 mm²
10.10 temperature rise the panel builder is responsible for the temperature rise calculation. eaton will provide heat dissipation data for the devices.
admissible back-up fuse - max 125 a gl/gg
voltage rating (ul csa 13) 480 y/277 v ac
mounting width per pole 17.5 mm
10.2.2 corrosion resistance meets the product standard's requirements.
10.2.7 inscriptions meets the product standard's requirements.
direction of incoming supply as required
mounting width 17.5 mm
product length/depth 80 mm
product width 54 mm
compliances ul csa09 (with supplementary protector only)
rohs conform
rated operational current for specified heat dissipation (in) 6 a
10.4 clearances and creepage distances meets the product standard's requirements.
10.12 electromagnetic compatibility is the panel builder's responsibility. the specifications for the switchgear must be observed.
current limiting class 3
amperage rating 6 a
terminal capacity of screw terminals for main cable 10 mm² (2x)
10.2.3.1 verification of thermal stability of enclosures meets the product standard's requirements.
rated short-circuit breaking capacity (iec 60947-2) at 400 v 15 ka
terminal protection finger and hand touch safe, dguv vs3, en 50274
special features ambient temperature hint: a 1 °c increase results in a 0.5% linear reduction of current carrying capacity
heat dissipation per pole, current-dependent 0 w
Features additional equipment possible
connectable conductor cross section (solid-core) - min 1 mm²
number of poles three-pole
10.6 incorporation of switching devices and components does not apply, since the entire switchgear needs to be evaluated.
10.5 protection against electric shock does not apply, since the entire switchgear needs to be evaluated.
used with faz
miniature circuit breaker
equipment heat dissipation, current-dependent 4.4 w
frequency rating - min 50 hz
10.2.6 mechanical impact does not apply, since the entire switchgear needs to be evaluated.
static heat dissipation, non-current-dependent 0 w
10.3 degree of protection of assemblies does not apply, since the entire switchgear needs to be evaluated.
number of poles (protected) 3
terminals (top and bottom) twin-purpose terminals
release characteristic d
busbar material thickness 0.8 mm - 2 mm
10.2.3.3 resist. of insul. mat. to abnormal heat/fire by internal elect. effects meets the product standard's requirements.
voltage rating 240 v ac / 415 v ac
connectable conductor cross section (solid-core) - max 25 mm²
Overvoltage category iii
10.7 internal electrical circuits and connections is the panel builder's responsibility.
rated impulse withstand voltage (uimp) 4 kv
voltage rating at dc 60 v dc (per pole)
rated switching capacity (iec/en 60947-2) 15 ka
connectable conductor cross section (multi-wired) - max 25 mm²
Type faz
miniature circuit breaker
10.2.4 resistance to ultra-violet (uv) radiation meets the product standard's requirements.
operational switching capacity 7.5 ka
rated operational voltage (ue) - max 400 v
rated insulation voltage (ui) 440 v
$42.29