Dimensions (W x L x H) | 18.9 x 76.6 x 124.3 mm | ||
Number of inputs | 4 | ||
Diagnostics via bus | Wire break Short circuit/overload in sensor supply Parameter errors Parameterisation error Overload at analogue inputs Upper limit value violated Overflow/underflow Lower limit value not observed | ||
Module parameters | Data format, analogue inputs Short circuit diagnostics for sensor supply Parameterisation error diagnostics Diagnostics of overload at analogue inputs Limit monitoring hysteresis Deactivate sensor supply Behaviour after overload on analogue inputs Behaviour after short circuit/overload | ||
Repetition accuracy | ±0.1% at 25°C | ||
Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 70 mA | ||
Basic error limit at 25 °C | ±0.2% | ||
Nominal DC operating voltage, electronics/sensors | 24 V | ||
Isolation channel - internal bus | yes | ||
Permissible voltage fluctuations for electronics/sensors | ± 25% | ||
KC mark | KC-EMV | ||
Certificate issuing authority | UL E239998 | ||
Shock resistance | Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27 | ||
Storage temperature | -20 °C ... 70 °C | ||
Degree of protection | IP20 | ||
Note on ambient temperature | -5 - 60°C for vertical installation | ||
Max. address volume, inputs | 8 Byte | ||
Data format | 15 bits + prefix Linear scaling | ||
Electrical connection input, function | Analogue input | ||
Electrical connection input, connector system | Spring-loaded terminal | ||
Electrical connection for input, conductor cross section | 0,2 mm² ... 1,5 mm² | ||
Electrical connection for input 2, function | Functional earth | ||
Electrical connection for input 2, connection technology | Spring-loaded terminal | ||
Electrical connection for input 2, connection pattern | 995,842 | ||
Electrical connection for input 2, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire end sleeves | ||
Note on materials | Contains paint-wetting impairment substances RoHS-compliant |
Grid dimension | 18,9 mm | ||
Diagnostics via LED | Errors per channel Errors per module | ||
Measured variable | Voltage Current | ||
Channel parameters | Wire break diagnostics Parameter error diagnostics Underflow/overflow diagnostics Upper limit diagnostics Lower limit diagnostics Smoothing factor Signal range per channel Lower/upper limits | ||
Fuse protection (short circuit) | Internal electronic fuse per module | ||
Operating error limit related to the ambient temperature range | ±0.3% | ||
Max. residual current of inputs per module | 1,4 A | ||
Power failure bridging | 10 ms | ||
Isolation channel - channel | no | ||
Approval | RCM trademark c UL us listed (OL) | ||
CE mark (see declaration of conformity) | To EU EMC Directive | ||
Vibration resistance | Transport application test with severity level 1 to FN 942017-4 and EN 60068-2-6 | ||
Corrosion resistance class CRC | 0 - No corrosion stress | ||
Relative air humidity | 95 % Non-condensing | ||
Ambient temperature | -5 °C ... 50 °C | ||
Product weight | 96 g | ||
analog input | -10 - 10 V -20 - 20 mA -5 - 5 V 0 - 10 V 0 - 20 mA 1 - 5 V 4 - 20 mA | ||
Max. cable length | 30 m Shielded | ||
Electrical connection input, connection type | 4x terminal strip | ||
Electrical connection input, number of connections/cores | 4 | ||
Electrical connection for input, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire end sleeves | ||
Electrical connection for input 2, connection type | Terminal strip | ||
Electrical connection for input 2, number of pins/wires | 4 | ||
Electrical connection for input 2, conductor cross section | 0,2 mm² ... 1,5 mm² | ||
Type of mounting | With H-rail | ||
Material housing | PA |