Dimensions (W x L x H) | 18.9 x 76.6 x 124.3 mm | ||
Number of outputs | 4 | ||
Diagnostics via bus | Short circuit/overload in actuator supply Short circuit/overload at analogue output Parameterisation error Nominal range exceeded Nominal range not reached Undervoltage in load supply General errors | ||
Module parameters | Deactivate actuator supply Data format for analogue outputs Short circuit diagnostics for actuator supply Parameterisation error diagnostics Diagnostics for undervoltage in load supply Behaviour after short circuit/overload in actuator supply Behaviour after short circuit/overload at analogue output | ||
Repetition accuracy | ±0.05% at 25°C | ||
Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 60 mA | ||
Operating error limit related to the ambient temperature range | ±0.3% | ||
Max. residual current outputs per module | 2 A | ||
Nominal operating voltage DC of load | 24 V | ||
Isolation channel - internal bus | yes | ||
Permissible voltage fluctuations for electronics/sensors | ± 25% | ||
Power supply, connection type | 2x terminal strip | ||
Power supply, number of pins/wires | 4 | ||
Power supply, conductor diameter | 0,2 mm² ... 1,5 mm² | ||
Approval | RCM trademark c UL us listed (OL) | ||
CE mark (see declaration of conformity) | To EU EMC Directive | ||
Vibration resistance | Transport application test with severity level 1 to FN 942017-4 and EN 60068-2-6 | ||
Corrosion resistance class CRC | 0 - No corrosion stress | ||
Relative air humidity | 95 % Non-condensing | ||
Degree of protection | IP20 | ||
Note on ambient temperature | -5 - 60°C for vertical installation | ||
Max. address volume, outputs | 8 Byte | ||
Data format | 15 bits + prefix Linear scaling | ||
Electrical connection output, function | Analogue output | ||
Electrical connection output, connector system | Spring-loaded terminal | ||
Electrical connection for output, conductor cross section | 0,2 mm² ... 1,5 mm² | ||
Electrical connection for output 2, function | Functional earth | ||
Electrical connection for output 2, connection technology | Spring-loaded terminal | ||
Electrical connection output 2, connection pattern | 995,842 | ||
Electrical connection output 2, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire end sleeves | ||
Note on materials | Contains paint-wetting impairment substances RoHS-compliant |
Grid dimension | 18,9 mm | ||
Diagnostics via LED | Errors per channel Errors per module | ||
Measured variable | Voltage Current | ||
Channel parameters | Force channel x Enable wire break/idling diagnostics Enable for parameterisation error diagnostics Enable overload/short circuit diagnostics Signal range per channel | ||
Fuse protection (short circuit) | Internal electronic fuse per module | ||
Intrinsic current consumption at nominal operating voltage load | Typically 15 mA | ||
Basic error limit at 25 °C | ±0.1% | ||
Nominal DC operating voltage, electronics/sensors | 24 V | ||
Power failure bridging | 10 ms | ||
Isolation channel - channel | no | ||
Permissible voltage fluctuation of load | ± 25 % | ||
power supply, connection system | Spring-loaded terminal | ||
Power supply, connection pattern | 995,847 | ||
Power supply, note on conductor diameter | 0.2 - 2.5 mm² for flexible conductors without wire end sleeves | ||
KC mark | KC-EMV | ||
Certificate issuing authority | UL E239998 | ||
Shock resistance | Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27 | ||
Storage temperature | -20 °C ... 70 °C | ||
Protection against direct and indirect contact | PELV | ||
Ambient temperature | -5 °C ... 50 °C | ||
Product weight | 96 g | ||
analog input | -10 - 10 V -20 - 20 mA -5 - 5 V 0 - 10 V 0 - 20 mA 4 - 20 mA | ||
Max. cable length | 30 m Shielded | ||
Electrical connection output, connection type | 4x terminal strip | ||
Electrical connection output, number of connections/cores | 4 | ||
Electrical connection for output, note on conductor cross section | 0.2 - 2.5 mm² for flexible conductors without wire end sleeves | ||
Electrical connection for output 2, connection type | Terminal strip | ||
Electrical connection output 2, number of pins/wires | 4 | ||
Electrical connection output 2, conductor cross section | 0,2 mm² ... 1,5 mm² | ||
Type of mounting | With H-rail | ||
Material housing | PA |