Material housing | Die-cast aluminium | ||
Field bus interface | 2x RJ45 push-pull socket, AIDA | ||
Parameterisation | Diagnostic behaviour Fail-safe response Forcing of channels Signal setup System parameter | ||
Additional functions | Acyclic data access via fieldbus Asynchronous data access via Ethernet Fast start-up (FSU) I&M Channel-oriented diagnostics via fieldbus LLDP MQTT MRP MRPD PROFIenergy PROFIsafe S2 system redundancy Start-up parameterisation in plain text via fieldbus System status can be mapped using process data Additional diagnostic interface for operator units | ||
Baud rate | 100 Mbit/s | ||
Intern power consumption nominal operating voltage | Typ. 70 mA | ||
Approval | RCM trademark | ||
Storage temperature | -20 °C ... 70 °C | ||
Ambient temperature | -5 °C ... 50 °C | ||
Max. address volume, outputs | 64 Byte | ||
Protocol | PROFINET IRT PROFINET RT | ||
LED display, product-specific | M: Modify, parameterisation PL: Load supply PS: Electronics supply, sensor supply SF: System fault |
Dimensions (W x L x H) | (incl. interlinking block) 50 x 107 x 80 mm | ||
Device-specific diagnostics | Channel-oriented and module-oriented diagnostics Undervoltage of modules Diagnostic memory | ||
Configuration support | GSDML file | ||
Operator controls | DIL switch | ||
Operational voltage range DC | 18 V ... 30 V | ||
Nominal operating voltage DC | 24 V | ||
Corrosion resistance class CRC | 0 - No corrosion stress | ||
Degree of protection | IP65 IP67 | ||
Product weight | 280 g | ||
Max. address volume, inputs | 64 Byte | ||
LED display, bus-specific | M/P: maintenance/PROFIenergy NF: Network fault TP1: Network active port 1 TP2: Network active port 2 | ||
Note on materials | RoHS-compliant |