Dimensions (W x L x H) | 27 x 123 x 40 mm | ||
Number of inputs | 8 | ||
Input debounce time | 0.1 ms | ||
Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 12 mA | ||
Nominal DC operating voltage, electronics/sensors | 24 V | ||
Isolation channel - internal bus | no | ||
Switching level | Signal 0: <= 5 V Signal 1: >= 11 V | ||
CE mark (see declaration of conformity) | To EU EMC Directive | ||
Shock resistance | Shock test with severity level 2 to FN 942017-5 and EN 60068-2-27 | ||
LABS (PWIS) conformity | VDMA24364-B1/B2-L | ||
Media temperature | -5 °C ... 50 °C | ||
Ambient temperature | -5 °C ... 50 °C | ||
Characteristic for inputs | To IEC 61131-2, type 3 | ||
Switching logic for inputs | PNP (positive switching) | ||
Electrical connection input, connection type | 8x socket | ||
Electrical connection input, number of connections/cores | 3 | ||
Material housing | PA-reinforced |
Grid dimension | 28 mm | ||
Diagnostics via LED | Errors per module Status per channel | ||
Fuse protection (short circuit) | Internal electronic fuse | ||
Max. residual current of inputs per module | 0,2 A | ||
Nominal operating voltage DC | 24 V | ||
Isolation channel - channel | no | ||
Permissible voltage fluctuations for electronics/sensors | ± 25% | ||
Vibration resistance | Transport application test with severity level 2 to FN 942017-4 and EN 60068-2-6 | ||
Corrosion resistance class CRC | 2 - Moderate corrosion stress | ||
Storage temperature | -20 °C ... 40 °C | ||
Degree of protection | IP65 IP67 | ||
Product weight | 75 g | ||
Max. cable length | 30 m | ||
Electrical connection input, function | Digital input | ||
Electrical connection input, connector system | M8x1, A-coded to EN 61076-2-104 | ||
Note on materials | RoHS-compliant |