Symbol | 992,256 | ||
Corrosion resistance class CRC | 2 - Moderate corrosion stress | ||
Setting range threshold value | 0 % ... 100 % | ||
Material housing | PA POM | ||
Pneumatic connection | QS-6 | ||
Type of mounting | With accessories | ||
Electrical connection | 3-wire Cable To EN 60947-5-2 | ||
Operational voltage range DC | 15 V ... 30 V | ||
Max. output current | 100 mA | ||
Switching function | Threshold value with fixed hysteresis | ||
Temperature coefficient in ± %FS/K | 0,05 %FS/K | ||
Ambient temperature | 0 °C ... 50 °C | ||
Note on operating and pilot medium | Lubricated operation possible | ||
End value for pressure measuring range | 10 bar | ||
Measurement method | Piezoresistive pressure sensor | ||
Note on materials | RoHS-compliant | ||
CE mark (see declaration of conformity) | To EU EMC Directive In accordance with EU RoHS Directive |
LABS (PWIS) conformity | VDMA24364-B1/B2-L | ||
Degree of protection | IP40 | ||
Switching status indication | Yellow LED | ||
Product weight | 47 g | ||
Mounting position | optional | ||
Cable length | 2,5 m | ||
Reverse polarity protection | For all electrical connections | ||
Short circuit current rating | yes | ||
Switching element function | N/O contact | ||
Switching output | NPN | ||
Repetition accuracy in ± %FS | 0,3 %FS | ||
Media temperature | 0 °C ... 50 °C | ||
Operating medium | Compressed air to ISO 8573-1:2010 [7:4:4] | ||
Start value for pressure measuring range | 0 bar | ||
Measured variable | Relative pressure | ||
CE marking (see declaration of conformity) | To UK instructions for EMC To UK RoHS instructions | ||
Approval | RCM trademark c UL us - Recognized (OL) |