Pollution degree | 3 | ||
CE mark (see declaration of conformity) | To EU EMC Directive In accordance with EU RoHS Directive | ||
Note on materials | RoHS-compliant | ||
Measuring principle | Inductive | ||
Switching output | NAMUR | ||
Max. switching frequency | 2.000 Hz | ||
Operational voltage range DC | 8,2 V | ||
Electrical connection 1, connection type | Plugs | ||
Electrical connection 1, design | Round | ||
Electrical connection 1, number of connections/cores | 8 | ||
Connectable nominal cross section conductor | 0,25 mm² ... 2,5 mm² | ||
Permissible cable diameter | 5 mm ... 13 mm | ||
Connection point for positioner and position sensor conforms to standard | VDI/VDE 3845 size AA 1 | ||
Product weight | 800 g | ||
Material housing | Die-cast aluminium | ||
Material shaft | High-alloy stainless steel | ||
Material mounting bracket | High-alloy stainless steel | ||
Material disc | High-alloy stainless steel | ||
Position indicator | Yellow/red | ||
Storage temperature | -20 °C ... 50 °C | ||
Shock resistance | Shock test with severity level 2 to FN 942017-5 and EN 60068-2-27 | ||
Corrosion resistance class CRC | 0 - No corrosion stress |
Approval | RCM trademark c CSA us (OL) | ||
KC mark | KC-EMV | ||
Safety Integrity Level (SIL) | SIL 2 | ||
Ambient temperature | -20 °C ... 80 °C | ||
Switching element function | N/C contact | ||
Max. output current DC | 3 mA | ||
Electrical connection | M12 | ||
Electrical connection 1, cable outlet | Straight | ||
Electrical connection 1, connector system | M12x1, A-coded to EN 61076-2-101 | ||
Electrical connection 1, connection pattern | 995,600 | ||
Cable fitting | M20x1.5 | ||
Dimensions (W x L x H) | 127 mm x 111 mm x 122 mm | ||
Mounting position | optional | ||
Housing colour | grey | ||
Material seals | NBR | ||
Material screws | High-alloy stainless steel | ||
Material snap ring | High-alloy stainless steel | ||
Material cover cap | PC | ||
Setting range of angular detection | 0 deg ... 90 deg | ||
Degree of protection | IP67 NEMA 4/4X | ||
Vibration resistance | Transport application test with severity level 2 to FN 942017-4 and EN 60068-2-6 | ||
LABS (PWIS) conformity | VDMA24364 zone III |